Suzhou Electric Appliance Research Institute
期刊号: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章检索

首页 >> 文章检索 >> 往年索引

±800 kV换流站可控消能装置电场仿真及试验验证

来源:电工电气发布时间:2022-03-24 13:24 浏览次数:597

±800 kV换流站可控消能装置电场仿真及试验验证

陶佳, 郑毅, 张科乾
(常州博瑞电力自动化设备有限公司,江苏 常州 213025)
 
    摘 要:特高压换流站内设备需要严格控制电极表面电场强度,以防止电晕放电现象。±800 kV 换流站用可控消能装置子单元较多,且处于不同电压等级,为准确了解各电极表面电场强度的分布情况,考虑计算及外绝缘试验的可行性,对可控消能装置建立了简化的三维模型,采用有限元分析中的直流传导场进行计算。通过初步仿真结果与试验结果对比分析,对模型中局放较高的部位进行结构优化。优化后的计算及试验结果表明了优化措施的合理性及直流场计算的准确性。
    关键词:换流站;可控消能装置;电场分布;仿真计算;结构优化;试验验证
    中图分类号:TM721.1     文献标识码:A     文章编号:1007-3175(2022)03-0046-04
 
Electric Field Simulation and Experimental Verification for Controllable
Energy Absorption Device in a ±800 kV Converter Station
 
TAO Jia, ZHENG Yi, ZHANG Ke-qian
(Changzhou Boil Electric Power Automation Equipments Co., Ltd, Changzhou 213025, China)
 
    Abstract: The equipment in the UHV converter station needs to strictly control the electric field strength on the electrode surface to prevent the corona discharge phenomenon.There are many controllable energy dissipation device sub-units used in ±800 kV converter stations,and they belong to different voltage levels.This paper established a simplified three-dimensional model of the controllable energy absorption device. It used the DC conduction field in the finite element analysis for calculation. To accurately understand the distribution of the electric field intensity on the surface of each electrode, the feasibility of calculation and external insulation test has been considered.Compared the preliminary simulation results with the test results, it optimized the structure of the parts with high partial discharge in the model. The optimized calculation and test results show the rationality of the optimization measures and the accuracy of the DC field calculation.
    Key words: converter station; controllable energy absorption device; electric field distribution; simulation calcuation; structure optimization;experimental verification
 
参考文献
[1] 常林晶,徐光辉,徐健涛,等.±1 100 kV 特高压阀厅金具表面电场计算及起晕校核[J] . 高压电器,2018,54(6) :88-90.
[2] 刘鹏,吴泽华,程建伟,等. 特高压多端柔直换流站直流场均压屏蔽金具电场分布仿真分析与差异化优化方法[J]. 电网技术,2020,44(1) :2-4.
[3] 毛艳,谷琛,魏杰,等.±800 kV 特高压换流站阀厅金具防晕设计尺寸研究[J] . 高压电器,2019,55(2) :9-11.
[4] 乐波,陈东,付颖,等.±1 100 kV 换流站直流场金具表面电场仿真静态场等效方法[J] . 电网技术,2017,41(11) :3428-3430.
[5] 姬大潜,刘泽洪,邓桃,等. 特高压直流输电系统稳态运行时高端阀厅内部的电场分析[J] . 高电压技术,2013,39(12) :3002-3004.
[6] 刘泽洪,王绍武,种芝艺,等. 适用于混合级联特高压直流输电系统的可控自恢复消能装置[J] . 中国电机工程学报,2021,41(2) :515-518.
[7] 马信山,张济世. 电磁场基础[M] . 北京:清华大学出版社,2004.
[8] 梁曦东. 高电压工程[M] . 北京:清华大学出版社,2003.
[9] 田冀焕,沙彦超,周远翔,等.800 kV 等级高压隔离开关的交、直流电场仿真计算[J] . 高电压技术,2011,37(5) :1216-1220.
[10] 韩社教,戴栋,马西奎,等. 应用有限元法计算氧化锌避雷器电位分布[J] . 中国电机工程学报,2001,21(12) :106-108.
[11] 孟晓波,卞星明,陈枫林,等. 负直流下绞线电晕起始电压分析[J]. 高电压技术,2011,37(1) :77-80.
[12] 易凡,杜志叶,黄从鹏,等. 负极性球板电晕放电下绝缘表面电荷分布特性研究[J] . 高压电器,2020,56(9) :198-200.
[13] 蒋兴良,林锐,胡琴,等. 直流正极性下绞线电晕起始特性及影响因素分析[J] . 中国电机工程学报,2009,29(34) :108-114.
[14] 齐磊,张静岚,符瑜科,等. 交直流复合电压下的稍不均匀场高压电极起晕特性[J] . 高电压技术,2017,43(9) :2993-2996.