一起500 kV断路器拒动故障原因分析及改进措施

来源:电工电气发布时间:2017-02-18 08:18 浏览次数:10
一起500 kV断路器拒动故障原因分析及改进措施
 
石万里,夏武
(中国南方电网超高压输电公司柳州局,广西 柳州 545006)
 
    摘 要:介绍了倒闸操作过程中5051 断路器分闸不成功事件过程,通过对该故障断路器进行拆分检查、测试及分析,指出该断路器发生轴承锈蚀导致合闸弹簧未完全释放,不能给分闸弹簧储能,是断路器分闸不成功的主要原因,针对此类断路器故障并从一次结构、二次信号回路等方面提出改进措施,避免了断路器拒动故障的发生。
    关键词:断路器;拒动;储能;改进
    中图分类号:TM561     文献标识码:A     文章编号:1007-3175(2017)02-0059-04
 
Analysis and Improvement Measures of Refusal-Operation Failure Cause of 500 kV Circuit Breaker
 
SHI Wan-li, XIA Wu
(Liuzhou Bureau of China Southern Power Grid Extra High Voltage Power Transmission Company, Liuzhou 545006, China)
 
    Abstract: Introduction was made to the refusal-operation of 5051 circuit breakers in the process of switching operation. This paper carried out splitting inspection, test and analysis for the malfunction circuit breaker and pointed out that the rusting bearings made the closing spring not completely released in the circuit breaker, which couldn’t store energy for the tripping spring, being the main reason of unsuccessful tripping of the circuit breaker. In allusion to this type of circuit breakers faults, the primary structure and the second signal circuits, this paper proposed improved measures, so as to prevent the circuit breakers refusal-operation from happening.
    Key words: circuit breaker; refusal-operation; stored energy; improvement
 
参考文献
[1] 宋宇. 断路器拒动故障原因分析及预防处理措施[J]. 现代制造,2014(30):40-41.
[2] 舒双焰,赵有铖,赵曼勇,等.“1.20”安顺电厂断路器拒动保护动作分析[J]. 电力系统保护与控制,2008,36(18):103-107.
[3] Q/CSG 10006—2004 电气操作导则[S].
[4] Q/CSG 21003—2008 中国南方电网电力调度管理规程[S].
[5] 金长军,杨绍露. 浅析防止500 kV断路器拒动的措施[J]. 黑龙江科技信息,2011(30):6.